0.6/1kV Unarmouered Low Voltage Cable to IEC60502 Standard CU/XLPE/PVC Cable

google facebook

BS5467 Standard 0.6/1kV Low Voltage/LV Armoured Underground Power Cable CU/XLPE/PVC/SWA/PVC Cables

CONSTRUCTION: 1. Stranded copper conductor class 2 2. XLPE insulation 3. PP Filling 4. Non-woven fabrics wrapping 5. PVC inner sheath 6. Steel wire armored 7. Non-woven fabrics wrapping 8. PVC outer sheath APPLICATION YJV32-Copper Conductor XLPE Insulated Steel Wire Armoured PVC Sheathed...

CONSTRUCTION:

1. Stranded copper conductor class 2

2. XLPE insulation

3. PP Filling

4. Non-woven fabrics wrapping

5. PVC inner sheath

6. Steel wire armored 

7. Non-woven fabrics wrapping

8. PVC outer sheath

APPLICATION

YJV32-Copper Conductor XLPE Insulated Steel Wire Armoured PVC Sheathed Power&Mains Cable.

Copper XLPE SWA PVC LSZH Cable is suitable for using in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 0.6/1kV.

CABLE STANDARDS

GB/T12706-2008,IEC,BS,VDE,ASTM and etc. upon request.



 image007.jpg image009.jpg

BASIC INFORMATION

Code Name 

YJV32

Rated Voltage (Uo/U)

0.6/1KV

Cable Structure

Copper Conductor / XLPE Insulation / Steel Wire Armoured / PVC Sheath

CONSTRUCTION

Conductor

Number of conductors:1,2,3,4,5,3+1,4+1

The conductors shall comply with the requirement given in IEC

Insulation

XLPE (Cross-linked Polyethylene) according to IEC

Sheath

PVC(Polyaluminium Chloride) according to IEC

Armoured

Steel Wire

CHARACTERISTICS

Conductor temperature

Maximum conductor temperature in normal use: 90℃

Max.short-circuit temperature

Maximum shall not exceed 250℃(5s Max,Duration)

Installation temperature

Ambient temperature under installation shall not be below 0℃

Minimum bending radius

The bending radius of cable: (D-Diameter of cable) 

————————————-≥15D

Description:



Nominal Cross Section

Diameter of Conductor (Approx.)

Nominal Insulation thickness

Nominal Inner Covering thickness

Nominal Alum Wire dia.

Nominal Sheath thickness

Overall Diameter (Approx.)

mm^2

mm

mm

mm

mm

mm

mm

1x4

2.3

0.7

1.0

0.8

1.8

10.9

1x6

2.8

0.7

1.0

0.8

1.8

11.4

1x10

3.6

0.7

1.0

0.8

1.8

12.2

1x16

4.5

0.7

1.0

0.8

1.8

13.1

1x25

5.6

0.9

1.0

0.8

1.8

14.6

1x35

6.7

0.9

1.0

1.25

1.8

16.6

1x50

8.0

1

1.0

1.25

1.8

18.1

1x70

9.4

1.1

1.0

1.25

1.8

19.7

1x95

11.0

1.1

1.0

1.6

1.8

22.0

1x120

12.4

1.2

1.0

1.6

1.8

23.6

1x150

13.8

1.4

1.0

1.6

1.8

25.4

1x185

15.3

1.6

1.0

1.6

1.8

27.4

1x240

17.5

1.7

1.0

1.6

1.9

29.9

1x300

19.5

1.8

1.0

2.0

2.0

33.1

1x400

22.6

2

1.2

2.0

2.2

37.3

1x500

25.2

2.2

1.2

2.0

2.3

40.5



Nominal Cross Section

Diameter of Conductor (Approx.)

Nominal Insulation thickness

Nominal Inner Covering thickness

Nominal Steel Wire dia.

Nominal Sheath thickness

Overall Diameter (Approx.)

mm^2

mm

mm

mm

mm

mm

mm

2x1.5

1.4

0.7

1.0

0.8

1.8

12.8

2x2.5

1.8

0.7

1.0

0.8

1.8

13.6

2x4

2.3

0.7

1.0

0.8

1.8

14.6

2x6

2.8

0.7

1.0

1.25

1.8

16.5

2x10

3.6

0.7

1.0

1.25

1.8

18.1

2x16

4.5

0.7

1.0

1.25

1.8

19.9

2x25

5.6

0.9

1.0

1.6

1.8

23.6

2x35

6.7

0.9

1.0

1.6

1.8

25.8

2x50

8.0

1

1.0

1.6

1.9

29.0

2x70

9.4

1.1

1.0

2.0

2.0

33.2

2x95

11.0

1.1

1.2

2.0

2.1

37.1

2x120

12.4

1.2

1.2

2.0

2.3

40.5

2x150

13.8

1.4

1.2

2.5

2.4

45.4

2x185

15.3

1.6

1.4

2.5

2.6

49.9

2x240

17.5

1.7

1.4

2.5

2.7

55.1

2x300

19.5

1.8

1.6

2.5

2.9

60.2

2x400

22.6

2

1.6

2.5

3.1

67.7



Nominal Cross Section

Diameter of Conductor (Approx.)

Nominal Insulation thickness

Nominal Inner Covering thickness

Nominal Steel Wire dia.

Nominal Sheath thickness

Overall Diameter (Approx.)

mm^2

mm

mm

mm

mm

mm

mm

3x1.5

1.4

0.7

1.0

0.8

1.8

13.2

3x2.5

1.8

0.7

1.0

0.8

1.8

14.1

3x4

2.3

0.7

1.0

0.8

1.8

15.2

3x6

2.8

0.7

1.0

1.25

1.8

17.1

3x10

3.6

0.7

1.0

1.25

1.8

18.9

3x16

4.5

0.7

1.0

1.25

1.8

20.8

3x25

5.6

0.9

1.0

1.6

1.8

24.7

3x35

6.7

0.9

1.0

1.6

1.8

27.2

3x50

8.0

1

1.0

1.6

1.9

30.6

3x70

9.4

1.1

1.0

2.0

2.1

35.2

3x95

11.0

1.1

1.2

2.0

2.2

39.3

3x120

12.4

1.2

1.2

2.0

2.3

43.0

3x150

13.8

1.4

1.4

2.5

2.5

48.6

3x185

15.3

1.6

1.4

2.5

2.7

53.0

3x240

17.5

1.7

1.4

2.5

2.8

58.5

3x300

19.5

1.8

1.6

2.5

3.0

64.0

3x400

22.6

2

1.6

3.15

3.3

73.5



Nominal Cross Section

Diameter of Conductor (Approx.)

Nominal Insulation thickness

Nominal Inner Covering thickness

Nominal Steel Wire dia.

Nominal Sheath thickness

Overall Diameter (Approx.)

mm^2

(3) mm

(1) mm

(3) mm

(1) mm

mm

mm

mm

mm

3x 16/10

4.5

3.6

0.7

0.7

1

1.6

1.8

22.7

3x 25/16

5.6

4.5

0.9

0.7

1

1.6

1.8

26.5

3x 35/16

6.7

4.5

0.9

0.7

1

1.6

1.9

29

3x 50/25

8.0

5.6

1

0.9

1

1.6

2.1

33

3x 70/35

9.4

6.7

1.1

0.9

1.2

2

2.2

38

3x 95/50

11.0

8.0

1.1

1

1.2

2

2.3

42.4

3x120/70

12.4

9.4

1.2

1.1

1.2

2

2.5

48.0

3x150/70

13.8

9.4

1.4

1.1

1.4

2.5

2.7

52

3x185/95

15.3

11.0

1.6

1.1

1.4

2.5

2.8

57.2

3x240/120

17.5

12.4

1.7

1.2

1.6

2.5

3.1

64

3x300/150

19.5

13.8

1.8

1.4

1.6

2.5

3.2

69.8

3x400/185

22.6

15.3

2

1.6

1.6

3.15

3.6

78.6



Nominal Cross Section

Diameter of Conductor (Approx.)

Nominal Insulation thickness

Nominal Inner Covering thickness

Nominal Steel Wire dia.

Nominal Sheath thickness

Overall Diameter (Approx.)

mm^2

mm

mm

mm

mm

mm

mm

4x1.5

1.4

0.7

1.0

0.8

1.8

14.0

4x2.5

1.8

0.7

1.0

0.8

1.8

14.9

4x4

2.3

0.7

1.0

1.25

1.8

17.0

4x6

2.8

0.7

1.0

1.25

1.8

18.2

4x10

3.6

0.7

1.0

1.25

1.8

20.2

4x16

4.5

0.7

1.0

1.6

1.8

23.0

4x25

5.6

0.9

1.0

1.6

1.8

26.7

4x35

6.7

0.9

1.0

1.6

1.9

29.5

4x50

8.0

1

1.0

2.0

2.1

34.2

4x70

9.4

1.1

1.2

2.0

2.2

38.8

4x95

11.0

1.1

1.2

2.0

2.3

42.9

4x120

12.4

1.2

1.4

2.5

2.5

48.6

4x150

13.8

1.4

1.4

2.5

2.7

53.2

4x185

15.3

1.6

1.4

2.5

2.8

58.1

4x240

17.5

1.7

1.6

2.5

3.1

64.8

4x300

19.5

1.8

1.6

2.5

3.2

70.4

4x400

22.6

2

1.8

3.15

3.6

81.3

Company Information:

1. Our factory specialized in manufacturing power/mains cable & electrical wire more than 19 years. 

2. Have Dezhou, Wuxi and Tengzhou 3 production bases and current employees more than 700 people. 

3. Supply power/mains cable & electrical wire to South America(Brazil...), East Asia(Korea...), Africa(Uganda, South Africa, Zimbabwe...), Southeast Asia(Myanmar, Thailand, Indonesia, Philippines, Malaysia, Cambodia...), Europe(Czech republic...) to global market. 

4. Had fixed partnership with SGCC&STATE GRID CORPORATION OF CHINA(China largest power enterprise) and many other our country State-owned big enterprise. 

5. Good quality(ISO/CCC/IEC/BS/VDE standard) and competitive price.

6. Standard export packing(Steel Iron drum, No-fumigation Iron wooden drum and Wooden drum). 


Contact:


Related Products
Home | About Us | Product | News | Knowledge | Contact Us | Mobile | XML

Copyright Shandong New Luxing Cable Co.,Ltd All rights reserved.

Shandong New Luxing Cable Co.,Ltd